空调系统中英文翻译内容摘要:
e refrigerants. Chilled Water Systems Chilled water systems were used in less than 4% of mercial buildings in the . in 1995. However, because chillers are usually installed in larger buildings, chillers cooled over 28% of the . mercial building floor space that same year (DOE, 1998). Five types of chillers are monly applied to mercial buildings: reciprocating, screw, scroll, centrifugal, and absorption. The first four utilize the vapor pression cycle to produce chilled water. They differ primarily in the type of pressor used. Absorption chillers utilize thermal energy (typically steam or bustion source) in an absorption cycle with either an ammoniawater or waterlithium bromide solution to produce chilled water. Overall System An estimated 86% of chillers are applied in multiple chiller arrangements like that shown in the figure (Bitondo and Tozzi, 1999). In chilled water systems, return water from the building is circulated through each chiller evaporator 7 where it is cooled to an acceptable temperature (typically 4 to 7176。 C) (39 to 45176。 F). The chilled water is then distributed to water toair heat exchangers spread throughout the facility. In these heat exchangers, air is cooled and dehumidified by the cold water. During the process, the chilled water increases in temperature and must be returned to the chiller(s). The chillers are watercooled chillers. Water is circulated through the condenser of each chiller where it absorbs heat energy rejected from the high pressure refrigerant. The water is then pumped to a cooling tower where the water is cooled through an evaporation process. Cooling towers are described in a later section. Chillers can also be air cooled. In this configuration, the condenserwould be a refrigeranttoair heat exchanger with air absorbing the heat energy rejected by the high pressure refrigerant. Chillers nominally range in capacities from 30 to 18,000 kW (8 to 5100 ton). Most chillers sold in the . are electric and utilize vapor pression refrigeration to produce chilled water. Compressors for these systems are either reciprocating, screw, scroll, or centrifugal in design. A small number of centrifugal chillers are sold that use either an internal bustion engine or steam drive instead of an electric motor to drive the pressor. The type of chiller used in a building depends on the application. For large office buildings or in chiller plants serving multiple buildings, centrifugal pressors are often used. In applications under 1000 kW (280 tons) cooling capacities, reciprocating or screw chillers may be more appropriate. In smaller applications, below 100 kW (30 tons), reciprocating or scroll chillers are typically used. Vapor Compression Chillers The nominal capacity ranges for the four types of electrically driven vapor pression chillers. Each chiller derives its name from the type of pressor used in the chiller. The systems range in capacities from the smallest scroll (30 kW。 8 tons) to the largest centrifugal (18,000 kW。 5000 tons).Chillers can utilize either an HCFC (R22 and R123) or HFC (R134a) refrigerant. The steady 8 state efficiency of chillers is often stated as a ratio of the power input (in kW) to the chilling capacity (in tons). A capacity rating of one ton is equal to kW or 12,000 btu/h. With this measure of efficiency, the smaller number is better. centrifugal chillers are the most efficient。 whereas, reciprocating chillers have the worst efficiency of the four types. The efficiency numbers provided in the table are the steady state fullload efficiency determined in accordance to ASHRAE Standard 30 (ASHRAE, 1995). These efficiency numbers do not include the auxiliary equipment, such as pumps and cooling tower fans that can add from to kW/ton to the numbers shown Chillers run at part load capacity most of the time. Only during the highest thermal loads in the building will a chiller operate near its rated capacity. As a consequence, it is important to know how the efficiency of the chiller varies with part load capacity. a representative data for the efficiency (in kW/ton) as a function of percentage full load capacity for a reciprocating, screw, and scroll chiller plus a centrifugal chiller with inlet vane control and one with variable frequency drive (VFD) for the pressor. The reciprocating chiller increases in efficiency as it operates at a smaller percentage of full load. In contrast, the efficiency of a centrifugal with inlet vane control is relatively constant until theload falls to about 60% of its rated capacity and its kW/ton increases to almost twice its fully loaded value. In 1998, the Air Conditioning and Refrigeration Institute (ARI) developed a new standard that incorporates into their ratings part load performance of chillers (ARI 1998c). Part load efficiency is expressed by a single number called the integrated part load value (IPLV). The IPLV takes data similar to that in Figure and weights it at the 25%, 50%, 75%, and 100% loads to produce a single integrated efficiency number. The weighting factors at these loads are , , , and , respectively. The equation to determine IPLV is: 9 Most of the IPLV is determined by the efficiency at the 50% and 75% part load values. Manufacturers will provide, on request, IPLVs as well as part load efficiencies. The four pressors used in vapor pression chillers are each briefly described below. While centrifugal and screw pressors are primarily used in chiller applications, reciprocating and scroll pressors are also used in smaller unitary packaged air conditioners and heat pumps. Reciprocating Compressors The reciprocating pressor is a positive displacement pressor. On the intake stroke of the piston, a fixed amount of gas is pulled into the cylinder. On the pression stroke, the gas is pressed until the dis。空调系统中英文翻译
相关推荐
单元、数据采集单元及计量表计等进行自动检测,并可实现远程维护和管理。 5. 系统主要设备技术要求 当量能量型 当量空调表 要求: 要求可以灵活计量到每一个末端,即: 需 监测并采集 每台风机盘管 的运行 状态和档位 数据。 要求用户可以直观查询使用量和总量。 要求可通过中央管理系统控制每一 只 的空调表,具备远程切断每户空调使用的功能。 要求整个系统不与水系统发生 关系 ,计量设备不得设置于户内
等 窗帘制作安装工程。 3 三、投标产品技术指标说明 本次投标产品 选用绍兴波力布艺有限公司生产的 80%遮光 亚麻布料作为窗帘面料,该产品完全符合国家标准 《消费品使用说明 纺织品和服装使用说明》 、 GB184012020《国家纺织产品基本安全技术规范》 及 GB/T198172020 《纺织品 装饰用织物》。 具备卓越的遮光及阻挡紫外线功能,主要技术指标如下: 成分: 80% 亚麻纤维 ,
测、案件查处。 二、 税收征管档案 信息化 管理 的优点 流程 规范 便于统一管理。 将征管资料档案的范围、分类、收集、立卷、归档、使用等要求以软件的形式编制在税收征管档案电子管理系统中,不按规定流程整理便无法归档,从而使征管资料档案化管理标准统一,要求规范。 解决了目前纸质征管档案资料管理中的标准不统一、内容不齐全,整理质量不高,整理的规格不统一等问题。 归档及时 保证资料完整。
B. 验证不合格时,检验员在物料上贴“不合格”标签,按《不合格控制程序》进行处理。 紧急放行 当生产急需来不及验证,在可追溯的前提下,由生产部填写《紧急(例 外)放行申请单》,经厂长批准后,一联留存,一联交 技质部 ,一联交仓库。 A. 仓库保管员根据批准的《紧急(例外)放行申请单》,按规定数量留取同批 样品送检,其余由检验员在领料单上注明“紧急放行”后放行;车间在其后