建筑给水排水毕业设计专业外文翻译内容摘要:

f trap seal depletion and the opportunity that exists for recharge on appliance discharge allow 25% depletion. The boundary equation may also be determined by local conditions: the AAV opening and subsequent loss coefficient depends on the local line pressure prediction. Empirical data identifies the AAV opening pressure, its loss coefficient during opening and at the fully open condition. Appliance trap seal oscillation is treated as a boundary condition dependent on local pressure. Deflection of the trap seal to allow an airpath to, or from, the appliance or displacement leading to oscillation alone may both be modelled. Reductions in trap seal water mass during the transient interaction must also be included. 3. Role of diversity in system operation In plex building drainage works the operation of the system appliances to discharge water to the work, and hence provide the conditions necessary for air entrainment and pressure transient propagation, is entirely random. No two systems will be identical in terms of their usage at any time. This diversity of operation implies that interstack venting paths will be established if the individual stacks within a plex building work are themselves interconnected. It is proposed that this diversity is utilized to provide venting and to allow serious consideration to be given to sealed drainage systems. In order to fully implement a sealed building drainage and vent system it would be necessary for the negative transients to be alleviated by drawing air into the work from a secure space and not from the external atmosphere. This may be achieved by the use of air admittance valves or at a predetermined location within the building, for example an accessible loft space. Similarly, it would be necessary to attenuate positive air pressure transients by means of PAPA devices. Initially it might be considered that this would be problematic as positive pressure could build within the PAPA installations and therefore negate their ability to absorb transient airflows. This may again be avoided by linking the vertical stacks in a plex building and utilizing the diversity of use inherent in building drainage systems as this will ensure that PAPA pressures are themselves alleviated by allowing trapped air to vent through the interconnected stacks to the sewer work. Diversity also protects the proposed sealed system from sewer driven overpressure and positive transients. A plex building will be interconnected to the main sewer work via a number of connecting smaller bore drains. Adverse pressure conditions will be distributed and the work interconnection will continue to provide venting routes. These concepts will be demonstrated by a multistack work. 4. Simulation of the operation of a multistack sealed building drainage and vent system Fig. 3 illustrates a fourstack work. The four stacks are linked at high level by a manifold leading to a PAPA and AAV installation. Water downflows in any stack generate negative transients that deflate the PAPA and open the AAV to provide an airflow into the work and out to the sewer system. Positive pressure generated by either stack surcharge or sewer transients are attenuated by the PAPA and by the diversity of use that allows one stacktosewer route to act as a relief route for the other stacks. (37K) Fig. 3. Four stack building drainage and vent system to demonstrate the viability of a sealed building system. The work illustrated has an overall height of 12 m. Pressure transients generated within the work will propagate at the acoustic velocity in air . This implies pipe periods, from stack base to PAPA of approximately s and from stack base to stack base of approximately s. In order to simplify the output from the simulation no local trap seal protection is included—for example the traps could be fitted with either or both an AAV and PAPA as examples of active control. Traditional works would of course include passive venting where separate vent stacks would be provided to atmosphere, however a sealed building would dispense with this venting arrangement. Ideally the four sewer connections shown should be to separate collection drains so that diversity in the sewer work also acts to aid system self venting. In a plex building this requirement would not be arduous and would in all probability be the norm. It is envisaged that the stack connections to the sewer work would be distributed and would be to a below ground drainage work that increased in diameter downstream. Other connections to the work would in all probability be from buildings that included the more traditional open vent system design so that a further level of diversity is added to offset any downstream sewer surcharge events of long duration. Similar considerations led to the current design guidance for dwellings. It is stressed that the work illustrated is representative of plex building drainage works. The simulation will allow a range of appliance discharge and sewer imposed transient conditions to be investigated. The following appliance discharges and imposed sewer transients are considered: 1. . discharge to stacks 1–3 over a period 1–6 s and a separate . discharge to stack 4 between 2 and 7 s. 2. A minimum water flow in each stack continues throughout the simulation, set at l/s, to represent trailing water following earlier multiple appliance discharges. 3. A 1 s duration stack base surcharge event is assumed to occur in stack 1 at s. 4. Sequential sewer transients imposed at the base of each stack in turn for s from 12 to 18 s. The simulation will demonstrate the efficacy of both the concept of active surge control and interstack venting in enabling the system to be sealed, . to have no high level roof perations and no vent stacks open to atmosphere outside the。
阅读剩余 0%
本站所有文章资讯、展示的图片素材等内容均为注册用户上传(部分报媒/平媒内容转载自网络合作媒体),仅供学习参考。 用户通过本站上传、发布的任何内容的知识产权归属用户或原始著作权人所有。如有侵犯您的版权,请联系我们反馈本站将在三个工作日内改正。